1.1kW – 500kW  /  1105 Inverter  

 

Overview

 

 

The 1105 digital AC inverter provides flexible, efficient and cost-effective solutions to a range of control needs.  It combines the latest IGBT-based PWM and digital-signal processor technologies with a revolutionary, patented digital-current regulator to deliver optimum performance, full programmability, and simplicity of operation. Compact and rugged, the inverter comes as an open chassis or in a NEMA 4 enclosure. Either type can be foot-mounted to a sub-plate or flange-mounted through a cutout, to dissipate heat outside an enclosure.

 
     

 

 

 

 

Performance Flexibility:

The 1105 offers performance capabilities to suit a broad range of applications where variable-frequency AC or conventional DC inverters are normally used. It can be configured for either constant-load, variable-load, or extended-load applications. A variety of general-purpose and application-engineered software options provide features optimized for specific customer requirements, such as blower and pump motors.

 

Digital Setup, Easy Operation:

The keypad and liquid crystal display provide a simple interface for setting and viewing operating parameters and diagnostics. All controller settings are made digitally through the keypad. Readouts and fault messages are displayed in plain language. A help feature provides on-line assistance at the touch of a button.

 

Power Quality:

The 1105 includes a built-in link choke that provides near-unity overall power factor at all motor speeds as well as low harmonic line currents.

 

Protection and Advanced Diagnostics:

The 1105 monitors its operating conditions and provides a comprehensive set of overload, short circuit, and other protective features. Faults are displayed in plain language along with the operating conditions at the time of occurrence. A log stores the last three faults as well as the buss voltage, motor current, output frequency, operating mode, and time of the most recent fault.

 

Serial Connectivity:

The 1105 features a fully-isolated EIA RS-422/485 serial interface that allows a process control computer, building automation system, or other host computer to set up, monitor, and control the drive using an ANSI standard protocol. An EIA RS-232 port is also available for direct connection to most types of personal computers. Optional DF1 and RTU protocols allow direct connection to Allen-Bradley and Modicon programmable controllers.


Features & Benefits:

 

General

   •  All-digital control for repeatable operation

  • 24-bit digital-signal processor (DSP) for fast, dynamic response

  • 8 kilobyte battery backup memory for application setup data

  • 48 kilobyte scratch pad memory and 1.5 megabyte firmware memory

  • Clock/calendar maintains accurate time during power outage

  • Sine-coded PWM or modified six-step waveform outputs for improved performance

  • High-switching-frequency IGBT devices for smooth, quiet operation

  • Digital current regulator for reduced fast response

  • Internal control loop for maintaining output during sudden load changes

  • Variable frequency control for simple applications

  • Integral DC link choke for high power factor and low total harmonic distortion

   •  Power-loss ride-through for reducing nuisance trips

  • Master-slave operation using either analog inputs or high-speed serial link

  • User-programmable analog and digital inputs and outputs

  • Ideal for applications requiring NEMA 4 enclosures

 

Ease of Installation, Setup, and Maintenance

   • Automated setup features do not require chart recorders or meters

  • Software calibration and adjustment eliminates tuning components

  • Digital parameter adjustment for precise and repeatable settings

  • Software input and output scaling eliminates potentiometers

  • Complete, self-contained package requires minimal option boards

  • Identical control boards across full power range reduce need for spare parts

 

Ease of Use

   • Touch keypad for easy parameter adjustment and access to displays

  • Two-line, descriptive, plain-language display

  • Numerical readouts and bar graph display

  • Comprehensive fault diagnostics displayed in plain language

  • Real-time information and three-fault log

  • Optional DriveLink™ software for managing multiple drives from a personal computer

 

Safe, Reliable Operation

   • Extensive electronic protection circuits

  • Tolerant of AC line voltage and frequency fluctuations

  • Multilevel security code prevents unauthorized parameter changes

  • Lockout of local operator controls, for safe remote operation


Electrical:

 

Input Supply

Voltage:                                     200 to 240 or 380 to 480 V AC, three-phase       

                                                Phase sequence insensitive

Voltage tolerance:                       –10% of minimum, +10% of maximum

Frequency:                                 47 to 63 Hz

Power factor:                              Displacement: 0.99 at all loads

                                                Overall: 0.94 at rated load

 

Output Rating

Voltage:                                     Zero to input supply voltage, three-phase

Frequency:                                

Switching frequency:                   Programmable from 2 to 10 kHz

Modifies six -step frequency:        Programmable from 0 to 10 kHz

 

Service Conditions

Efficiency:                                  97% nominal at rated switching frequency

Overload current:                       

 

Environmental

 

Operating temperature:                 32° to 104° F (0° to 40° C)

Storage temperature:                    5° to 158° F (–15° to 70° C)

Operating humidity:                     95% maximum, non-condensing

Altitude:                                    To 3,300 ft. (1,000 m) without de-rating

 

 

Performance

 

Frequency Control

Range:                                       Zero to base speed at full current output

            PWM Sinewave              Base speed to 300 Hz at constant power

            Six Step                                    0 to 10 Khz

Resolution:                                 0.20% with analog input (10-bit)

0.1  Hz with digital input

 

 

Inputs and Outputs

 

Analog Inputs

20 MHz control:                                     Three (3) 12-bit analog inputs (0 to +10 V DC, ±10 V DC, and 4 to 20 mA)

40 MHz control:                                     Three (3) 12-bit analog inputs (±10 VDC or 4 to 20 mA)

                                            

 

Analog Outputs

20 MHz control:                                     Two (2) 12-bit analog outputs (±10 VDC)

40 MHz control:                         Two (2) 12-bit analog outputs (±10 VDC and 4 to 20 mA)

                                               

 

Digital Inputs

20 MHz control:                         Eleven (11) digital inputs (sink of 1 mA to common)

40 MHz control:                         Twelve (12) digital inputs (source of 8 mA from 24 VDC)

                                               

 

Digital Outputs

20 MHz control:                                     Three (3) standard digital outputs (Form C contact rated 250 VAC @ 5 A,

                                                Form A contact rated 250 VAC @ 5 A, and open-collector driver rated 24 VDC @ 500 mA)

40 MHz logic I/O control:             Three (3) digital outputs (Form A contact rated 250 VAC @ 5 A)

40 MHz contact I/O control:         Six (6) alternative digital outputs (open-collector drivers rated 24 VDC@ 500 mA)

                                               

 

 

 

 

 

 

 

 

 

 

Serial Communications

Asynchronous port:                     EIA RS-232 and RS-422/485, isolated, 0.3 to 19.2 kbaud

                                                ANSI-x3.28-2.5-A4 protocol standard; 

                                                Optional Allen-Bradley DF1, Modicon RTU, and

                                                Johnson Controls N2 protocols

Synchronous port:                      EIA RS-485 for high-speed master/slave networking

 

 

Typical Parameters and Displays:

 

Programmable Parameters

   • Set point                      • User I/O parameter selections  

   • Set point minimum        • S-ramp profile smoothing 

   • Set point maximum       • Switching frequency        

   • Set point units label,      • Master / slave select / source  

   • Scaling, precision          • Slave ratio / position phasing  

   • Set point source            • Keypad enable                

   • (3) skip frequencies       • Security code                 

   • (3) skip bandwidths                                             

   • Minimum / maximum                                           

   • Current limit                                                       

   • Restart retries / delay                                           

   • Analog I/O scaling / polarity                                    

   • User analog input mode                                       

 

Status Displays

   • Buss voltage                • Energy consumption        

   • Power factor                 • Accumulated thermal load 

   • Output current              • Accumulated time run      

   • Output frequency          • Fault log and conditions   

   • Power consumption       • Input status

 

 

Protection

 

      •  Ground fault                                     •  Power transistor fault

      •  Output phase-to-phase short circuit      •  Logic power under-voltage

      •  DC buss over-voltage                        •  Remote command signal loss

      •  DC buss under-voltage                       •  Memory malfunction

      •  Instantaneous over-current                  •  Processor not running fault

      •  Output overload                                •  Synchronous serial error

      •  Heat sink over-temperature                

      •  Ambient over-temperature                           

 

 

 

Power Range

 

   Input        Constant-Torque            Variable-Torque           Extended-Torque

   Voltage     Applications                  Applications                Applications

   230 VAC  11/2-15 hp (1.1-11 kW)  2-20 hp (1.5-15 kW)   —

   380 VAC  11/2-25 hp (1.1-18 kW)  2-30 hp (1.5-22 kW)   —

   460 VAC  11/2-25 hp (1.1-18 kW)  2-30 hp (1.5-22 kW)   25-40 hp (18-30 kW)